- Sprinklers
- Water spray fire extinguishing
- Foam fire extinguishing
- Fire department hydrants
- High performance with a smallest bore with our specifically designed fire pump based on the new firefighting regulation in Japan.
- High performance and efficiency with satisfying all items of the new technical standard of Japanese firefighting regulation.
- Easy maintenance and inspection due to totally packaged products according to the Firefighting law in Japan.
Liquid
Fluid quality: Clean water
Fluid temperature: 0~40°C (No freezing)
Materials
Impeller: Aluminum Bronze
Shaft: SUS420J2Q or SUS403
Casing: KTGF: FC、KTGDF: FCD
Motor
Type: TEFC indoor (18.5 kW or less), ODP (22kW or more)
Power source: Three phase
Speed: 50Hz: 1,500 min-1, 60Hz: 1,800 min-1
|
|
Installation location
Installation location: Indoor
Structure
Impeller: Closed
Shaft sealing: KTGF: Gland packing, KTGDF: Mechanical seal
Bearing: Closed ball bearing
Flange figure
Flange figure: KTGF: JIS10K standard, KTGDF: JIS20K
Coating color (Munsell No.)
Coating color (Munsell No.): Vermillion (7.5R4/14)
- Escape orifice: with sluice valve (orifice dia.: 3mm)
- Check valve
- Sluice valve: with Indicator
- Pipe for performance test: with Flow meter, Sluice valve
- Pressure gage: Class 1.6 or more φ100
- Compound gage: Class 1.6 or more φ100
- Foot valve: In case KTGF
- Suction reducer: In case KTGF
- Suction cover: In case KTGF
- Connecting pipe
- Flexible joint: Approved by the Firefighting Equipment and Safety Center of Japan
- Priming tank: In case KTGF
- Pressure tank for activation: In case KTGF200
- Control panel: ECKD type
- Pump: with Motor shaft coupling, Coupling guard
Foundation bolt
|